Gallery
Size: | 3 |
Switching (1-pole or 3-pole): | 3-pole |
Weight [kg]: | 3.98 |
Rated operational current Un= 690V [A]: | 630 |
Conventional thermal current Ith [A]: | 630 |
Rated operational voltage Ue [V]: | 690 |
Rated insulation voltage Ui [V]: | 1000 |
Rated impuls withstand voltage Uimp [V]: | 8000 |
Rated frequency [Hz]: | 50 |
Utilization category Ue= 400V: | AC-23B |
Utilization category Ue= 690V: | AC-22B |
Utilization category Ue= 440V DC: | DC-21B |
Mechanical durability [cycles]: | 1000 |
Permissible ambient air temperature [°C]: | -25 +55 |
Type of protection: | IP 3X |
Maximum power dissipation of he NH Fuse -Links [W]: | 48 |
Busbar mounting: | By hooks |
Terminal side: | Top or bottom |
Terminal connection: | Box terminal |
Fuses status monitoring: | Mechanical |
Type of mounting: | 60mm busbar system |
Alternative products
-
BERÜHRUNGSSCHUTZ GR.3 SILAS
Import code: 36952-0010
13,30 €
-
NACHRÜSTS. AC23 GR.1-3 SILAS (1SATZ=3ST)
Import code: 36953-0010
46,90 €
-
1SATZ (2ST) BLENDSTREIFEN GR.1-3 SILAS
Import code: 36940-0010
5,10 €
-
1 SATZ KONTAKTHAKEN EDURO
Import code: 36959-0060
11,90 €
-
STROMDIEBSTAHLSICHERUNG GR.000-3 SILAS
Import code: 36969-0010
5,20 €